Danfoss EV220B 6 - 22
EV220B 6-22 is a direct servo-operated 2/2-way solenoid valve
program with connections from 1/4" to 1".
This program is especially for OEM applications demanding a
robust solution and moderate flow rates.
- 2/2-way
- Servo-operated
- DN 6 - DN 22
- Brass or DZR (de-zincification resistant) brass valve body
- NC (normally closed) and NO (normally open) versions
- ISO 228/1 or NPT thread connection (EVSI and EVSI-U)
- Click for the
Danfoss EV220B 6-22 data sheet.
EV220B 6-22 Technical Data
Differential pressure range |
|
0.1 / 0.3 to 20 bar (30 bar gas to DN 10) |
Ambient temperature: |
|
40 to 80oC Max,
depending on coil type |
Media temperature: |
|
EPDM : -30oC - +100oC
(with AR coil (Ex m II T4) generally max +50oC
|
Materials: |
|
Valve body : Brass |
|
|
Seals : EPDM or FKM |
Code No.
(without coil) |
End Connection |
Kv Value (m3/h) |
Orifice (mm) |
Seal* Material |
Type designation |
Differential pressure (bar based on
coil BB max. |
Main type |
Specification |
min. |
Max a.c. |
d.c. |
|
032U1236+ |
G 1/4 |
0.7 |
6 |
EPDM |
EV220B6B |
G14ENC000 |
0.1 |
20 |
10 |
|
032U1237 |
G 1/4 |
0.7 |
6 |
FKM |
EV220B6B |
G14FNC000 |
0.1 |
20 |
10 |
|
032U1242+ |
G 3/8 |
1.5 |
10 |
EPDM |
EV220B10B |
G38ENC000 |
0.1 |
20 |
10 |
|
032U1246 |
G 3/8 |
1.5 |
10 |
FKM |
EV220B10B |
G38FNC000 |
0.1 |
20 |
10 |
|
032U1251+ |
G 1/2 |
1.5 |
10 |
EPDM |
EV220B10B |
G12ENC000 |
0.1 |
20 |
10 |
|
032U1252 |
G 1/2 |
1.5 |
10 |
FKM |
EV220B10B |
G12ENC000 |
0.1 |
20 |
10 |
|
032U1256+ |
G 1/2 |
2.5 |
12 |
EPDM |
EV220B12B |
G12FNC000 |
0.1 |
20 |
10 |
|
032U1255 |
G 1/2 |
2.5 |
12 |
FKM |
EV220B12B |
G12NC000 |
0.1 |
20 |
10 |
|
032U1261+ |
G 3/4 |
6 |
18 |
EPDM |
EV220B18B |
G34ENC000 |
0.3 |
10 |
- |
|
032U1260 |
G 3/4 |
6 |
18 |
FKM |
EV220B18B |
G34ENC000 |
0.3 |
10 |
- |
|
032U1263 |
G 1 |
6 |
22 |
EPDM |
EV220B22B |
G1ENC000 |
0.3 |
10 |
- |
|
032U1266 |
G1 |
6 |
22 |
FKM |
EV220B22B |
G1FNC000 |
0.3 |
10 |
- |
|
*EPDM seals for use on water, glycol and steam
NC - Normally closed versions, NO - normally open versions (in
specification code)
+WRAS approved
Coil also required for complete product, see coil types BA, BB, BE
and BG.